Now showing items 1-2 of 2

    • Measurement stand for study properties of isolation materials using polarization method 

      Zukowski, P.; Koltunowicz, T.; Kozak, Cz.; Kierczynski, K.; Rogalski, P. (БНТУ, 2014)
      The article presents measurement stand, which is used to measure polarization and depolarization currents, using PDC method, in wet transformer oil-impregnated cellulose isolation. Maximum resolution of measured currents reaches 10-15 A. The accuracy of thermal stabilization, in three-electrode capacitor system, comes to 0,001 °C.
      2014-08-25
    • Measurement Stand, Method and Results of Composite Electrotechnical Pressboard-Mineral Oil Electrical Measurements 

      Rogalski, P. (БНТУ, 2020)
      The paper presents a measuring stand designed and built for testing direct and alternating current properties of power transformers basic insulation component i.e. electrotechnical pressboard impregnated with transformer oil. Measurements of direct and alternating current parameters are performed using the frequency domain spectroscopy and polarization depolarization current ...